A
t l a n t a H o m e I n s p e
c t o r s
- Grading does not slope away
from the foundation. Lots should be graded
to drain surface water away from foundation walls. The grade away from foundation walls
shall fall a minimum of 6" within the first 10 feet. (2006 International Residential
Code R401.3)
- Grading might hold ground
water. The code requires all
drainage to be diverted away from the yard. Surface drainage shall be diverted to a
storm sewer conveyance or other point of collection. (2006 International Residential Code
R401.3)
- Foundations with improperly
compacted fill. Could probe under the
footings. Fill soil that support footings and foundations shall be designed, installed
and tested in accordance with accepted engineering practices. (2006 International
Residential Code R401.2)
- No vapor barrier present for a
concrete slab. This could allow
water or moisture problems in the basement. A 6 mil (0.006 inch; 152 ìm) polyethylene or approved vapor retarder with joints lapped not
less than 6 inches (152 mm) shall be placed between the concrete floor slab and the base
course or the prepared subgrade where no base course exists.
(2006 International Residential Code R506.2.3)
- Improper wall bracing
for a 1 or 2 story structure. The corner exterior walls are missing proper
bracing. All
exterior walls shall be braced in accordance with this section. (2006 International
Residential Code R602.10)
- Improper wall bracing for a 3
story structure. The corner exterior
walls are missing proper bracing. All exterior corner walls shall be braced at each
corner and at least every 25 feet with a minimum of 48" of approved structural
sheathing. (2006 International Residential Code R602.10)
- Exterior windows and
doors do not have properly installed flashing and weep holes at the brick.
Flashing is required above all doors and windows installed in brick and prevents water
from soaking behind the brick running into the structure. Without weep holes to drain the
water to the outside, flashing serves no purpose. Flashing and weepholes
are required at all brick shelf angles over all doors and windows. (2006 International
Residential Code R703.8)
- Exterior wood not properly
protected. Some of the exterior
wood has open joints which will allow moisture to enter and will cause deterioration. Some
of the paint is peeling off the wood trim. The trim may not be properly primed to bond the
paint to the wood. Proper caulking and painting are needed. All exterior walls shall be
covered with approved materials designed and installed to provide a barrier against the
weather. (2006 International Residential Code R703.1)
- Exterior wood siding
trim not properly caulked or sealed at the brick or concrete foundation walls to prevent
water and moisture from damaging the wood. Water will run behind the wood and
cause deterioration. (2006 International Residential Code R703.1)
- Some of the exterior
cement siding has recessed nails. Recessed nails loose
their holding strength in fiber cement siding. All
manufacturers require the nails to be flush and not recessed. The recessed nails should be
caulked and another flush nail installed next to it. (2006 International Residential
Code R104.9)
- Exterior openings in the
structure are not sealed. This will allow
air leaks into the structure. All exterior joints in the building envelope, that are
sources of air leaks, shall be caulked, gasketed,
weather-stripped or otherwise sealed in an approved manner. (2000 International Energy
Code 502.1.4.2)
- Chimney height is not tall
enough. This could be a
potential fire hazard. All chimneys shall extend 2 higher than any portion of
roof within 10 and at least 3 higher than the roof penetration. (2006
International Residential Code R1003.9)
- Roof shingles have toe board
nail holes present. Toe boards are walk
boards the roofers use. Any holes in the shingles could turn into a roof leak. All
shingles with holes should be replaced or sealed with a sealant that will last as long as
the shingles. Recommend sealing the shingles with a one part urethane sealant similar to Sonnaborne RP-1. The proper procedure in sealing the holes is to
raise the shingle and install the sealant under the hole. Then the shingle is mashed flat
and the sealant should run out the hole. Roof shingles shall provide a barrier against
the weather to protect its supporting elements and structure beneath. (2006 International
Residential Code R901.1)
- Roof shingles are
missing roofing felt at the sheathing along the eaves. This protects the roof
sheathing. Starting at the eave, apply 36 inch wide sheets of underlayment...(2006
International Residential Code R905.2.7)
- Step flashing is missing at
sloped vertical walls. Some of the roof
flashing at the vertical walls is continuous flashing. Flashing prevents water from
entering at the intersection of the wall and the roof. Continuous flashing was used
successfully for many years. However, step flashing is a far superior method of flashing
and is required for all roofing. Flashing against a vertical sidewall shall be the
step-flashing method. (2006 International Residential Code R905.2.8.4)
- Deck footings are
smaller than the minimum allowable size of 12" x 12". See Section
R403.1.1 Minimum size. The size of footings supporting piers and columns shall be based
on the tributary loads and allowable soil pressure in accordance with Table R401.4.1.
(2006 International Residential Code R403.1.1)
- Deck footings do not extend
12" below grade. All footings must be
below the frost line. All exterior footings shall be placed at least 12 inches below
the undisturbed gound surface. (2006 International Residential
Code R403.1.4)
- Deck stair handrail is not the
correct size. Handrails that are 2x4
or larger are too large to be used for handrails since the cannot
be gripped. Handrails shall have either a circular cross section with a diameter of 1
1/4" to 2", or a noncircular cross section with a perimeter dimension of at
least 4" but not more than 6 1/4" and a largest cross section dimension not
exceeding 2 3/4". Edges shall have a minimum radius of 1/8". (2006 International
Residential Code R311.5.6.3)
- Exterior deck is missing
properly installed flashing. Flashing prevents
water from entering behind the deck and into the structure. Flashing is required where
decks attach to a wall or floor assembly of wood frame construction. Exterior
balconies, decks and porches shall be flashed in accordance with Section 703.8. (2006
International Residential Code R703.8(5))
- Some of the roof framing
has ridge beams that are too small and do not extend to the bottom of the rafters.
The ridge must extend down to the bottom of the rafters to properly support the rafters. The
ridge shall not be less in depth than the cut end of the rafters. (2006 International
Residential Code R802.3)
- Roof purlin supports, supporting the rafters, are double 2x4s which are
not the proper size. The purlins should be single 2x6s
turned perpendicular to the rafters which are stronger and less expensive than flat double
2x4s. Purlins shall be sized no less than the size of the
rafters they support. (2006 International Residential Code R802.5.1)
- Some of the rafter purlins support post exceed 48 inches
apart. Additional support post are required to properly support the purlins.
All rafter purlins must be braced every 48 inches to a load
bearing wall or support. (2006 International Residential Code R802.5.1)
- Some of the rafter purlins are spliced between the support post. Support members
are not allowed to be spliced without additional support installed. All purlins should be spliced directly above a support post. Purlins must be continuous between braces. (2006 International
Residential Code R802.5.1)
- Roof framing support
members have "V" joint or bird mouth splices that are not properly reinforced or
supported by a support post to a load bearing wall below. All load bearing beams
must be supported at any splice. Roof framing shall be capable of supporting all loads
imposed and shall transmit the resulting loads to its supporting structural elements.
(2006 International Residential Code R801.2)
- Attic is missing
flooring from the end of the attic stairs to the furnace. This makes it dangerous
to climb over the stairs to access the flooring at the furnace. All attics must have an
unobstructed, floored passageway 22" wide x 30" high to the furnace. (2006
International Residential Code M1305.1.3)
- Attic insulation
certification card is missing. This is required to verify the attic has the proper
amount of insulation. The insulation installer shall provide a signed and dated
certification for the insulation installed, listing the type of insulation, the
manufacturer and the R-value. (2000 International Energy Code Section 102.5.1)
- Attic insulation
thickness markers are missing. One thickness marker is required every 300 s.f. of floor area. The thickness of roof/ceiling blown insulation
shall be identified by thickness markers. (2000 International Energy Code Section
102.5.1.1)
- Attic insulation is not deep
enough. Sometimes the
insulation settles and is not deep enough. The insulation installer certifies the minimum
thickness of the insulation". (2000 International Energy Code Section 502.2.3.2)
- Attic is missing firestopping at an open chase. A chase is an opening in the
attic floor that could allow a fire, from the story below, to enter the attic. All
openings in the attic floor need sealing with drywall. Firestopping
is required at each floor, at the attic floor and at all roof penetrations. (2006
International Residential Code R602.8)
- Basement ceiling needs firestopping around all pipe penetrations. Firestopping prevents a fire from spreading to different parts of
the structure. Firestopping is required at all openings
around vents, pipes, ducts, chimneys and fireplaces at ceiling and floor levels, with
noncombustible materials. (2006 International Residential Code R602.8)
- Doors and windows are
missing shims and anchors along the jambs. All doors and windows need shimming
along the jambs (sides) and proper anchorage for a proper installation. Materials,
equipment and devices approved by the building official shall be constructed and installed
in accordance with such approval. (2006 International Residential Code R104.9)
- Bedroom windows not
large enough to be used for an emergency exit. Each bedroom shall have an operable
window with a sill height no more than 44" above the floor. Minimum clear height of
22" or minimum width of 20". The net clear opening shall be 4 square
feet. (2006 International Residential Code R310.1)
- Fireplace has wood trim
within too close to the opening. Wood too close to the opening is a fire hazard
and could catch fire. Woodwork or other combustible materials shall not be placed
within 6 inches of a fireplace opening. Combustible material within 12 inches of the
fireplace opening shall not project more than1/8 inch for each 1 inch distance from such
opening. (2006 International Residential Code R1001.11)
- Step heights or tread
depths are not the proper size. These are potential trip hazards. The maximum
allowable step height is 7 3/4". The minimum allowed depth of the tread is 9".
(2006 International Residential Code R311.5.3)
- Step heights or tread
widths vary in a flight of stairs. The different step heights or widths could be a
trip hazard. Risers (heights) and treads (widths) may not vary more than 3/8".
(2006 International Residential Code R311.5.3)
- Stair tread nosing or
overhang extends too far over the step below. The edge of the steps could break
with the grain of the wood allowing someone to fall down the stairs. The maximum
allowable overhang is 1 1/4". (2006 International Residential Code R311.5.3.3)
- Top basement step is not deep
enough.
Sometimes the oak flooring overhangs the top tread too far. This is a potential trip
hazard. The minimum allowed depth of the tread is 9". The maximum allowable
projection or nosing is 1 1/4". (2006 International Residential Code R311.5.3)
- Front door is missing a
landing just outside the door. A minimum of 3 foot landing shall be required on
each side of an egress door. (2006 International Residential Code R311.4.3)
- Door to the basement is
missing a door sweep and weather-stripping. Unconditioned air can enter the
conditioned space. Any opening from a conditioned space to a non-conditioned space must be
weather-stripped or sealed. (2000 International Energy Code Section 502.1.4.2)
- Basement ceiling height is too
low. Basement ceiling ducts
are too low and will prevent installing a ceiling at the proper height. Habitable rooms
shall have a ceiling height of not less than 7 feet 6 inches. Furred areas shall have a
ceiling height of not less than 7 feet. (2006 International Residential Code R305.1)
- Garage floor does not
slope enough to prevent liquids from running under the walls. Flammable liquids
could run under the walls into the structure and be ignited by the basement furnace or
water heater. That area of floor used for parking of automobiles or other vehicles
shall be sloped to facilitate the movement of liquids to a drain or toward the main
vehicle entry doorway. (2006 International Residential Code R309.3)
- Garage furnace and water
heater gas piping is not protected from possible impact. An automobile could hit
the piping and cause a gas leak. The pipe must be protected from possible impact. (2006
International Residential Code G2422.1.1)
- Ground fault circuit
interrupter electrical outlet is missing at a wet location. Any electrical outlet
located in the bathrooms, kitchen counter area, unfinished basement, garage or on the
exterior of the structure that can be reached from the ground, must be GFCI protected. (2005
NEC 210-8(6))
- Ground fault circuit
interrupter electrical outlet is missing at a sink. Any electrical outlet located
within 6 feet of a sink or basin must be GFCI protected. (2005 NEC 210-8(b))
- No heating and air
conditioning damper system present to balance the heating and air conditioning. A two story structure
with a single heat and air conditioning system, will find it difficult to balance the heat
and cooling. A readily accessible manual or automatic damper system shall be provided
to partially restrict or shut off the heating and/or cooling input to each zone or floor.
(2000 International Energy Code Section 503.3.3.7)
- Furnace ductwork not
proper sealed to prevent air leakage in nonconditioned areas.
Sometimes the duct insulation is sealed, but the actual ducts are not sealed. All ducts
must be sealed at the furnace and at the register boots. All joints shall be
securely fastened and sealed with welds, gaskets, mastic adhesives,
mastic-plus-embedded-fabric systems or tapes. (2000 International Energy Code Section
503.3.4.3)
- Attic furnace does not
have the required working platform in front of the furnace for servicing. This
makes it difficult to service the unit or change the filter. A working platform,
30" deep with a clear headroom of 30" high, is
required along the control side of the furnace. (2006 International Residential Code
M1305.1.3)
- Range is missing
anti-tip brackets on the rear feet to prevent tipping over. All manufacturers supply anti-tip brackets with all free standing
ranges to prevent tipping. A heavy object such as a turkey can be placed on the open door
causing the range to tip spilling hot liquids from the burners. (2006 International
Residential Code R104.9)
- Attic pull down stair is
missing weather-stripping. Unconditioned attic
air can enter the conditioned space. Any opening from a conditioned space to a
non-conditioned space must be weather-stripped or sealed. (2000 International Energy Code
Section 502.1.4.2).
- Attic stair is not
insulated and is the largest source of heat loss and heat gain thru the attic.
Recommend installing an insulated cover over the stair. Insulated covers can be purchased
from Battic Door at (508) 320-9082 or www.batticdoor.com. (2000
International Energy Code Section 502.1.4.2)
If you have
additional questions, E-Mail
us. 
Christian
Building Inspectors, Inc., 3697 Habersham Lane, Duluth, Georgia 30096-6111, Office
1-888-257-0365 or 770-849-0920
Home Page | 200% Guarantee | 90
Day Home Warranty | Atlanta Information | Atlanta Top Real Estate
Agents | Building
Product Defects | Class Action Lawsuits | Frequently Asked Questions
| Home Tips Newsletters | How To Choose A Home
Inspector | Mold
Problems | New Home
Construction Problems| Online Scheduling | Photos Of Defects | Pre-Inspection Agreement | Radon Testing | Recall Chek | Related Links | Sample Report | Synthetic Stucco (EIFS)
Problems | Virtual Tour A Home
Inspection