A
t l a n t a H o m e I n s p e c t o r
- Grading does not slope
away from the foundation. Lots should be graded to drain surface water away from
foundation walls. The grade away from foundation walls shall fall a
minimum of 6" within the first 10 feet. (2006 International
Residential Code R401.3)
- Grading might hold
ground water. The code requires all drainage to be diverted away
from the yard. Surface drainage shall be diverted to a storm sewer
conveyance or other point of collection. (2006 International Residential
Code R401.3)
- Foundations with
improperly compacted fill. Could probe under the footings. Fill soil that
support footings and foundations shall be designed, installed and tested
in accordance with accepted engineering practices. (2006
International Residential Code R401.2)
- No vapor barrier present
for a concrete slab. This could allow water or moisture problems in the
basement. A 6 mil (0.006 inch; 152 ěm) polyethylene or approved vapor
retarder with joints lapped not less than 6 inches (152 mm) shall be
placed between the concrete floor slab and the base course or the prepared
subgrade where no base course exists. (2006 International Residential Code
R506.2.3)
- Improper wall bracing
for a 1 or 2 story structure. The corner exterior
walls are missing proper bracing. All
exterior walls shall be braced in accordance with this section. (2006 International
Residential Code R602.10)
- Improper wall bracing
for a 3 story structure. The corner exterior walls are missing proper bracing. All
exterior corner walls shall be braced at each corner and at least every 25
feet with a minimum of 48" of approved structural sheathing. (2006
International Residential Code R602.10)
- Exterior windows and
doors do not have properly installed flashing and weep holes at the brick. Flashing is required
above all doors and windows installed in brick and prevents water from
soaking behind the brick running into the structure. Without weep holes to
drain the water to the outside, flashing serves no purpose. Flashing
and weepholes are required at all brick shelf angles over all doors and
windows. (2006 International Residential Code R703.8)
- Exterior wood not
properly protected. Some of the exterior wood has open joints which will
allow moisture to enter and will cause deterioration. Some of the paint is
peeling off the wood trim. The trim may not be properly primed to bond the
paint to the wood. Proper caulking and painting are needed. All
exterior walls shall be covered with approved materials designed and
installed to provide a barrier against the weather. (2006 International
Residential Code R703.1)
- Exterior wood siding
trim not properly caulked or sealed at the brick or concrete foundation
walls to prevent water and moisture from damaging the wood. Water will run behind
the wood and cause deterioration. (2006 International Residential Code
R703.1)
- Some of the exterior
cement siding has recessed nails. Recessed nails loose
their holding strength in fiber cement siding. All manufacturers require
the nails to be flush and not recessed. The recessed nails should be
caulked and another flush nail installed next to it. (2006
International Residential Code R104.9)
- Exterior openings in the
structure are not sealed. This will allow air leaks into the structure. All
exterior joints in the building envelope, that are sources of air leaks,
shall be caulked, gasketed, weather-stripped or otherwise sealed in an
approved manner. (2000 International Energy Code 502.1.4.2)
- Chimney height is not
tall enough. This could be a potential fire hazard. All chimneys
shall extend 2’ higher than any portion of roof within 10’ and at least 3’
higher than the roof penetration. (2006 International Residential Code
R1003.9)
- Roof shingles have toe
board nail holes present. Toe boards are walk boards the roofers use. Any holes
in the shingles could turn into a roof leak. All shingles with holes
should be replaced or sealed with a sealant that will last as long as the
shingles. Recommend sealing the shingles with a one part urethane sealant
similar to Sonnaborne RP-1. The proper procedure in sealing the holes is
to raise the shingle and install the sealant under the hole. Then the
shingle is mashed flat and the sealant should run out the hole. Roof
shingles shall provide a barrier against the weather to protect its
supporting elements and structure beneath. (2006 International Residential
Code R901.1)
- Roof shingles are
missing roofing felt at the sheathing along the eaves. This protects the roof
sheathing. Starting at the eave, apply 36 inch wide sheets of
underlayment...(2006 International Residential Code R905.2.7)
- Step flashing is missing
at sloped vertical walls. Some of the roof flashing at the vertical walls is
continuous flashing. Flashing prevents water from entering at the
intersection of the wall and the roof. Continuous flashing was used
successfully for many years. However, step flashing is a far superior
method of flashing and is required for all roofing. Flashing against a
vertical sidewall shall be the step-flashing method. (2006 International
Residential Code R905.2.8.4)
- Deck footings are
smaller than the minimum allowable size of 12" x 12". See Section R403.1.1
Minimum size. The size of footings supporting piers and columns shall
be based on the tributary loads and allowable soil pressure in accordance
with Table R401.4.1. (2006 International Residential Code R403.1.1)
- Deck footings do not
extend 12" below grade. All footings must be below the frost line. All
exterior footings shall be placed at least 12 inches below the undisturbed
gound surface. (2006 International Residential Code R403.1.4)
- Deck stair handrail is
not the correct size. Handrails that are 2x4 or larger are too large to be
used for handrails since the cannot be gripped. Handrails shall have
either a circular cross section with a diameter of 1 1/4" to 2",
or a noncircular cross section with a perimeter dimension of at least
4" but not more than 6 1/4" and a largest cross section
dimension not exceeding 2 3/4". Edges shall have a minimum radius of
1/8". (2006 International Residential Code R311.5.6.3)
- Exterior deck is missing
properly installed flashing. Flashing prevents water from entering behind the deck
and into the structure. Flashing is required where decks attach to a wall
or floor assembly of wood frame construction. Exterior balconies, decks
and porches shall be flashed in accordance with Section 703.8. (2006
International Residential Code R703.8(5))
- Some of the roof framing
has ridge beams that are too small and do not extend to the bottom of the
rafters.
The ridge must extend down to the bottom of the rafters to properly
support the rafters. The ridge shall not be less in depth than the cut
end of the rafters. (2006 International Residential Code R802.3)
- Roof purlin supports,
supporting the rafters, are double 2x4s which are not the proper size. The purlins should be
single 2x6s turned perpendicular to the rafters which are stronger and
less expensive than flat double 2x4s. Purlins shall be sized no less
than the size of the rafters they support. (2006 International Residential
Code R802.5.1)
- Some of the rafter
purlins support post exceed 48 inches apart. Additional support post
are required to properly support the purlins. All rafter purlins must
be braced every 48 inches to a load bearing wall or support. (2006
International Residential Code R802.5.1)
- Some of the rafter
purlins are spliced between the support post. Support members are not
allowed to be spliced without additional support installed. All purlins
should be spliced directly above a support post. Purlins must be
continuous between braces. (2006 International Residential Code R802.5.1)
- Roof framing support
members have "V" joint or bird mouth splices that are not
properly reinforced or supported by a support post to a load bearing wall
below.
All load bearing beams must be supported at any splice. Roof framing
shall be capable of supporting all loads imposed and shall transmit the
resulting loads to its supporting structural elements. (2006 International
Residential Code R801.2)
- Attic is missing
flooring from the end of the attic stairs to the furnace. This makes it dangerous
to climb over the stairs to access the flooring at the furnace. All
attics must have an unobstructed, floored passageway 22" wide x
30" high to the furnace. (2006 International Residential Code
M1305.1.3)
- Attic insulation
certification card is missing. This is required to
verify the attic has the proper amount of insulation. The insulation
installer shall provide a signed and dated certification for the
insulation installed, listing the type of insulation, the manufacturer and
the R-value. (2000 International Energy Code Section 102.5.1)
- Attic insulation
thickness markers are missing. One thickness marker is
required every 300 s.f. of floor area. The thickness of roof/ceiling blown
insulation shall be identified by thickness markers. (2000
International Energy Code Section 102.5.1.1)
- Attic insulation is not
deep enough. Sometimes the insulation settles and is not deep
enough. The insulation installer certifies the minimum thickness of the
insulation". (2000 International Energy Code Section 502.2.3.2)
- Attic is missing
firestopping at an open chase. A chase is an opening
in the attic floor that could allow a fire, from the story below, to enter
the attic. All openings in the attic floor need sealing with drywall. Firestopping
is required at each floor, at the attic floor and at all roof
penetrations. (2006 International Residential Code R602.8)
- Basement ceiling needs
firestopping around all pipe penetrations. Firestopping prevents a
fire from spreading to different parts of the structure. Firestopping
is required at all openings around vents, pipes, ducts, chimneys and
fireplaces at ceiling and floor levels, with noncombustible materials.
(2006 International Residential Code R602.8)
- Doors and windows are
missing shims and anchors along the jambs. All doors and windows
need shimming along the jambs (sides) and proper anchorage for a proper
installation. Materials, equipment and devices approved by the building
official shall be constructed and installed in accordance with such
approval. (2006 International Residential Code R104.9)
- Bedroom windows not
large enough to be used for an emergency exit. Each bedroom shall have
an operable window with a sill height no more than 44" above the
floor. Minimum clear height of 22" or minimum width of
20". The net clear opening shall be 4 square feet. (2006 International
Residential Code R310.1)
- Fireplace has wood trim
within too close to the opening. Wood too close to the
opening is a fire hazard and could catch fire. Woodwork or other
combustible materials shall not be placed within 6 inches of a fireplace
opening. Combustible material within 12 inches of the fireplace opening
shall not project more than1/8 inch for each 1 inch distance from such
opening. (2006 International Residential Code R1001.11)
- Step heights or tread
depths are not the proper size. These are potential
trip hazards. The maximum allowable step height is 7 3/4". The
minimum allowed depth of the tread is 9". (2006 International
Residential Code R311.5.3)
- Step heights or tread
widths vary in a flight of stairs. The different step
heights or widths could be a trip hazard. Risers (heights) and treads
(widths) may not vary more than 3/8". (2006 International Residential
Code R311.5.3)
- Stair tread nosing or
overhang extends too far over the step below. The edge of the steps
could break with the grain of the wood allowing someone to fall down the
stairs. The maximum allowable overhang is 1 1/4". (2006
International Residential Code R311.5.3.3)
- Top basement step is not
deep enough. Sometimes the oak flooring overhangs the top tread too
far. This is a potential trip hazard. The minimum allowed depth of the
tread is 9". The maximum allowable projection or nosing is 1
1/4". (2006 International Residential Code R311.5.3)
- Front door is missing a
landing just outside the door. A minimum of 3 foot
landing shall be required on each side of an egress door. (2006
International Residential Code R311.4.3)
- Door to the basement is
missing a door sweep and weather-stripping. Unconditioned air can
enter the conditioned space. Any opening from a conditioned space to a
non-conditioned space must be weather-stripped or sealed. (2000
International Energy Code Section 502.1.4.2)
- Basement ceiling height
is too low. Basement ceiling ducts are too low and will prevent
installing a ceiling at the proper height. Habitable rooms shall have a
ceiling height of not less than 7 feet 6 inches. Furred areas shall have a
ceiling height of not less than 7 feet. (2006 International Residential Code
R305.1)
- Garage floor does not
slope enough to prevent liquids from running under the walls. Flammable liquids could
run under the walls into the structure and be ignited by the basement
furnace or water heater. That area of floor used for parking of automobiles
or other vehicles shall be sloped to facilitate the movement of liquids to
a drain or toward the main vehicle entry doorway. (2006 International
Residential Code R309.3)
- Garage furnace and water
heater gas piping is not protected from possible impact. An automobile could hit
the piping and cause a gas leak. The pipe must be protected from possible
impact. (2006 International Residential Code G2422.1.1)
- Ground fault circuit
interrupter electrical outlet is missing at a wet location. Any electrical outlet
located in the bathrooms, kitchen counter area, unfinished basement,
garage or on the exterior of the structure that can be reached from the
ground, must be GFCI protected. (2005 NEC 210-8(6))
- Ground fault circuit
interrupter electrical outlet is missing at a sink. Any electrical outlet
located within 6 feet of a sink or basin must be GFCI protected. (2005
NEC 210-8(b))
- No heating and air
conditioning damper system present to balance the heating and air
conditioning. A two story structure with a single heat and air
conditioning system, will find it difficult to balance the heat and
cooling. A readily accessible manual or automatic damper system shall
be provided to partially restrict or shut off the heating and/or cooling
input to each zone or floor. (2000 International Energy Code Section
503.3.3.7)
- Furnace ductwork not
proper sealed to prevent air leakage in nonconditioned areas. Sometimes the duct
insulation is sealed, but the actual ducts are not sealed. All ducts must
be sealed at the furnace and at the register boots. All joints
shall be securely fastened and sealed with welds, gaskets, mastic
adhesives, mastic-plus-embedded-fabric systems or tapes. (2000
International Energy Code Section 503.3.4.3)
- Attic furnace does not
have the required working platform in front of the furnace for servicing. This makes it difficult
to service the unit or change the filter. A working platform, 30"
deep with a clear headroom of 30" high, is required along the control
side of the furnace. (2006 International Residential Code M1305.1.3)
- Range is missing
anti-tip brackets on the rear feet to prevent tipping over. All manufacturer’s
supply anti-tip brackets with all free standing ranges to prevent tipping.
A heavy object such as a turkey can be placed on the open door causing the
range to tip spilling hot liquids from the burners. (2006 International
Residential Code R104.9)
- Attic pull down stair is
missing weather-stripping. Unconditioned attic air can enter the conditioned
space. Any opening from a conditioned space to a non-conditioned space
must be weather-stripped or sealed. (2000 International Energy Code
Section 502.1.4.2).
- Attic stair is not
insulated and is the largest source of heat loss and heat gain thru the
attic.
Recommend installing an insulated cover over the stair. Insulated covers
can be purchased from Battic Door at (508) 320-9082 or www.batticdoor.com.
(2000 International Energy Code Section 502.1.4.2)
If
you have additional questions, E-Mail us. 

Christian
Building Inspectors, Inc., 3697 Habersham Lane, Duluth, Georgia 30096-6111,
Office 770-849-0920, Fax 770-849-0540
Home Page | 200% Guarantee
| Atlanta Information | Building Product
Defects | Class Action Lawsuits | Frequently Asked
Questions | Home Tips
Newsletters | Home Warranty
| How To Choose A
Home Inspector | Mold Problems | New Home
Construction Problems| Photos Of
Defects | Radon Testing
| Synthetic Stucco
(EIFS) Problems | Virtual Tour A Home
Inspection